-40%

HONEYWELL Resideo S89E1058, S89E-1058, S89E 1058 DIRECT SPARK IGNITION MODULE

$ 116

Availability: 24 in stock
  • Brand: Honeywell
  • Model: S89E 1058
  • Condition: New
  • MPN: S88E 1058

    Description

    HONEYWELL
    S89E 1058 Primary Control
    Direct Spark Control
    DSI Control
    DUAL ROD DIRECT SPARK IGNITION MODULE, 100% SHUTOFF WITH LOCKOUT,
    REQUIRES EXTERNAL 120 VAC SPARK TRANSFORMER, 2 AMP GAS VALVE, 24 VAC.
    4 SECOND
    LOCKOUT.
    S89E1009 HONEYWELL FUNCTIONAL S89E1033 HONEYWELL FUNCTIONAL
    Features
    • Controls ignition sequence and gas control
    operation in direct spark ignition systems.
    • Control separate 120 Vac spark generator
    that provides high voltage potential for main
    burner ignition.
    • Lockout after one trial for ignition if main
    burner fails to ignite.
    • Reset from thermostat after lockout.
    Use separate electrodes for spark ignition
    and flame sensing.
    • Use any 24 Vac combination gas control
    designed for direct spark applications
    and rated at 2.0A or less.
    Product Specifications
    Ignition System Type
    Direct Spark Ignition
    Ignition Sequence
    Single trial for main burner ignition
    (then shut down and lockout)
    Typical Gas Control
    VR8205, VR8305
    Type of Gas
    Natural or LP
    Flame Sense
    Two Rod
    Ignition Source
    External (120 VAC powered)
    High Voltage Spark Generator
    PrePurge
    Ignition Trials To Lockout
    1
    Lockout Timing
    4 sec.
    Ignition Trial Time (sec)
    4 sec.
    Maximum Valve Load @ 24 Vac (Amps)
    2A
    Typical Ignition Hardware
    Q652, Q345
    Dimensions (in.)
    5 1/4 in. high x 4 1/16 in. wide
    x 1 15/16 in. long
    Dimensions (mm)
    133 mm high x 103 mm wide
    x 49 mm deep
    Electrical Ratings
    24 Vac
    Frequency
    60 Hz
    Maximum Ambient Temperature (F)
    -40 F to +175 F
    Maximum Ambient Temperature (C)
    -40 C to +79 C
    Approvals, Canadian Standards Association
    Design Certified
    Flame Failure Response Time (sec)
    2.0 sec. @ 2.5 microamp
    Flame Failure Re-ignition Time (sec
    Please note some of the items require
    professional
    knowledge
    and skills to
    handle
    or installed.
    homas New Parts is not
    responsible
    for any
    damage
    or injuries
    resulted
    from mishandling of
    professiona
    l
    products.
    All HVACR equipment should be
    serviced
    installed
    by certified professionals only.
    Please let us know if you have any
    concerns or questions.